Skid Mounted Portable Unit Substation with the following major components:
Reconditioned Square D 15KV Switchgear with a Main 600 amp Fused Load Interrupter Switch, three each 600 amp Feeder Load Interrupter Switches and one New General Electric PowerVac 1200 amp Fixed Vacuum Circuit Breaker
New Cooper 1500 KVA Pad Mount Transformer 13800Delta-13800Y/7967 volt, three phase
Neutral Grounding Resistor
Control components included a 5 KVA CPT, Schweitzer SEL-751 Feeder Protection Relay, and Startco SE-325 NGR Monito